YASKAWA HV600 Technical Reference page 426

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.13 Y: Application Features
When the PI Aux Feedback increases to more than the YF-12 level, the digital output set for H2-xx = 9F [MFDO
Function Selection = High PI Auxiliary Control Level] will immediately activate. When the level decreases to less
than the YF-12 level, the digital output will immediately deactivate.
1 : Alarm Only
When the PI Aux Feedback increases to more than YF-12 level, the keypad will show an HIAUX [High PI Aux
Feedback Level] alarm and the digital output set for H2-xx = 9F will activate. When the feedback decreases to less
than YF-12 level, the drive will clear the alarm and the digital output will deactivate.
2 : Fault
When the output frequency is more than zero, and the PI Aux Feedback increases to more than YF-12 level, the digital
output set for H2-xx = 9F and an HIAUX alarm will immediately activate. If the feedback stays more than the YF-12
level for the time set in YF-13 [PI Aux High Level Detection Time], the drive will then detect an HIAUX [High PI Aux
Feedback Level] fault.
3 : Auto-Restart (time set by YF-15)
When the output frequency is more than zero, and the PI Aux Feedback increases to more than YF-12 level, the digital
output set for H2-xx = 9F and an HIAUX alarm will immediately activate. If the feedback stays more than the YF-12
level for the time set in YF-13, the drive will then detect an HIAUX fault.
When L5-01 [Number of Auto-Restart Attempts] > 0 and if the drive detects an HIAUX fault, the drive will
automatically try an Auto-Restart after YF-15 [PI Aux Level Detect Restart Time] is expired. If the feedback is not
less than the YF-12 level, the Auto-Restart counter will increment and the drive will stay faulted.
YF-15: PI Aux Level Detect Restart Time
No.
Name
(Hex.)
YF-15
PI Aux Level Detect Restart
Time
(3F5E)
YF-16: PI Auxiliary Control P Gain
No.
Name
(Hex.)
YF-16
PI Auxiliary Control P Gain
(3F5F)
RUN
YF-17: PI Auxiliary Control I Time
No.
Name
(Hex.)
YF-17
PI Auxiliary Control I Time
(3F60)
RUN
Note:
Set this parameter to 0.0 to disable the integrator.
YF-18: PI Aux Control Detect Time Unit
No.
Name
(Hex.)
YF-18
PI Aux Control Detect Time
Unit
(3F61)
0 : Minutes (min)
1 : Seconds (sec)
426
Sets the length of time the drive will wait before it tries an Auto-Restart of LOAUX [Low PI Aux
Feedback Level] or HIAUX [High PI Aux Feedback Level] fault.
Sets the proportional gain for the suction pressure control.
Sets the integral time for the suction pressure control.
Sets the time unit for YF-10 [PI Aux Control Low Lvl Det Time] and YF-13 [PI Aux High Level
Detection Time].
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
5.0 min
(0.1 - 6000.0 min)
Default
(Range)
2.00
(0.00 - 25.00)
Default
(Range)
5.0 s
(0.0 - 360.0 s)
Default
(Range)
1
(0, 1)