YASKAWA HV600 Technical Reference page 585

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.
Connect the power supply connector.
A - Cooling fan
2.
Align the pins on the fan unit base with the notches on the fan and put the fan unit base in the fan unit, then
use the screws to safety it.
Tighten the screws to a correct tightening torque:
• 0.98 N∙m to 1.33 N∙m (8.67 in∙lb to 11.77 in∙lb)
A - Cooling fan
B - Fan unit base
3.
Safety the fan cable through the clamp.
A - Clamp
4.
Put the fan unit into the specified location and slide it to the left, then use screws to safety it to the drive.
Tighten the screws to a correct tightening torque:
• 0.98 N∙m to 1.33 N∙m (8.67 in∙lb to 11.77 in∙lb)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
8.4 Replace Drive Cooling Fans and Circulation Fans
B - Fan unit base
Figure 8.57 Connect the Power Supply Connector
C - Alignment pin on fan unit base
D - Circulation fan connector
Figure 8.58 Install the Cooling Fan
Figure 8.59 Safety the Fan Cable
8
585