Enclosed Model Specifications - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

7.4
208 V Enclosed Model Specifications
Model
Maximum Applicable Motor Output (HP)
Rated Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Rated Output Current (A)
Minimum Applicable Motor
Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency
(Hz)
Harmonics
Input Power (kVA)
Reduction
Filter (IEC/EN 61800-3
EMC
Category 2)
*1
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*3
Carrier frequency is 5 kHz. You must derate the current to increase the carrier frequency.
Model
Maximum Applicable Motor Output (HP)
Rated Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Rated Output Current (A)
Minimum Applicable Motor
Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency
(Hz)
Harmonics
Input Power (kVA)
Reduction
Filter (IEC/EN 61800-3
EMC
Category 2)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 7.5 208 V Enclosed Ratings
D002
D003
*2
0.5
0.75
3.8
4.9
2.4
3.5
*3
*3
1.5
1.5
Table 7.6 208 V Enclosed Ratings
D024
*2
7.5
25.6
24.2
*3
3.75
7.4 208 V Enclosed Model Specifications
D004
D007
1
6.0
8.9
Three-Phase 208 Vac 50/60 Hz
-15 to 10%
±5%
4.6
7.5
*3
*3
1.5
1.5
110% of rated output current for 60 s
150% peak
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Three-Phase 208 Vac
240 Hz
Built-in
Built-in
D030
D046
10
15
32.2
48.6
Three-Phase 208 Vac 50/60 Hz
-15 to 10%
±5%
30.8
46.2
*3
*3
3.75
7.5
110% of rated output current for 60 s
150% peak
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Three-Phase 208 Vac
240 Hz
Built-in
Built-in
D010
2
3
12.0
10.6
*3
1.5
D059
D074
20
61.8
59.4
*3
7.5
D016
5
18.1
16.7
*3
3.75
25
77.2
74.8
*3
15
7
533

Advertisement

Table of Contents
loading

Table of Contents