9.17 Z: Bypass Parameters
Setting Value
Function
6
READY
7
RUN Active
8
Drive RUN active
9
Bypass RUN active
10
HAND mode Active
11
OFF mode Active
12
Auto mode Active
13
Drive Mode Selected
14
Bypass Mode Selected
15
Fault Active
16
Drive Fault Active
17
Bypass Fault Active
18
Auto Transfer Active
19
Serial Run Active
20
Damper Actuator Output
21
ON Always
22
Loss of Load Detected
23
Run Verify Active
24
Soft Starter Run
Command
25
Safeties Closed
26
Mirror HV600 M1-M2
27
Mirror HV600 M3-M4
28
Mirror HV600 M5-M6
99
Not Used
670
System ready.
Drive run or bypass run active.
The digital output activates when the system is in Drive Mode and the HV600 drive is running.
ON : Running in Drive Mode
OFF : Not running or in Bypass Mode
The digital output activates when the system is in Bypass Mode and is running. Contactor K3 is closed.
ON : Running in Bypass Mode
OFF : Not running or in Drive Mode
The digital output activates when the system is running in HAND Mode during Drive Mode and Bypass Mode.
ON : Running in HAND Mode
OFF : Not running or in AUTO Mode
The digital output activates when the HAND/OFF/AUTO selection is in OFF Mode or if system is faulted. It is also
active when in Emergency Override Mode.
ON : System is in OFF Mode or is faulted
OFF : HAND Mode, AUTO Mode (even if not running), Emergency Override.
The digital output activates when the HAND/OFF/AUTO selection is in AUTO Mode. It will activate when the system
is running and when the system is not running and in Drive Mode and Bypass Mode.
ON : System is in AUTO Mode
OFF : HAND Mode, OFF Mode, Faulted, Emergency Override
The digital output activates when Drive Mode is selected. It stays active during Remote Transfer to Bypass,
Emergency Override Bypass, Energy Savings, Fault condition, and when the system is not running.
ON : Drive Mode is selected
OFF : Bypass Mode is selected
The digital output activates when Bypass Mode is selected. It stays active during Emergency Override Drive, Fault
condition, and when the system is not running.
ON : Bypass Mode is selected
OFF : Drive Mode is selected
Set when there is an active Drive fault or Bypass fault.
There is a fault in the HV600 drive.
There is a fault in the bypass.
There is a drive fault that activated Auto Transfer to Bypass.
Serial Communications is commanding a RUN.
System commanded to RUN in Drive Mode or Bypass Mode.
This digital output is always active.
The motor current is less than the set value/values.
The digital output closes when the drive or bypass output current is more than 10% of E2-01.
The digital output opens when the drive or bypass output current is less than 5% of E2-01.
Controls the soft starter Run command to ramp down the soft starter before it opens bypass contactor K3.
All of the programmed safety digital inputs are satisfied.
The digital output activates when the HV600 drive digital output (M1-M2) is closed.
ON : Digital Output M1-M2 on HV600 is closed
OFF : Digital Output M1-M2 on HV600 is open
The digital output activates when the HV600 drive digital output (M3-M4) is closed.
ON : Digital Output M3-M4 on HV600 is closed
OFF : Digital Output M3-M4 on HV600 is open
The digital output activates when the HV600 drive digital output (M5-M6) is closed.
ON : Digital Output M5-M6 on HV600 is closed
OFF : Digital Output M5-M6 on HV600 is open
This setting allows serial communications to control the output.
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Ref.
449
449
449
449
449
449
449
450
450
450
450
450
450
450
450
449
451
451
451
451
451
451
452
452