YASKAWA HV600 Technical Reference page 514

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

6.8 Auto-Tuning Errors
Code
Name
Er-02
Drive in an Alarm State
Code
Name
Er-03
OFF Button was Pressed
Code
Name
Er-04
Line-to-Line Resistance Error
Code
Name
Er-05
No-Load Current Error
Code
Name
Er-08
Rated Slip Error
514
Causes
The motor nameplate data entered during Auto-
Tuning is incorrect.
You did Auto-Tuning while the drive had a minor
fault or alarm.
There is a defective motor cable or cable connection.
The load is too large.
The drive detected a minor fault during Auto-Tuning.
Causes
You pushed
during Auto-Tuning.
Causes
The Auto-Tuning results were not in the applicable
parameter setting range.
Auto-Tuning did not complete in a pre-set length of
time.
There is a defective motor cable or cable connection.
The motor nameplate data entered during Auto-
Tuning is incorrect.
Causes
The Auto-Tuning results were not in the applicable
parameter setting range.
Auto-Tuning did not complete in a pre-set length of
time.
The motor nameplate data entered during Auto-
Tuning is incorrect.
Rotational Auto-Tuning was done with a load that
was more than 30% of the rating connected to the
motor.
Causes
The motor nameplate data entered during Auto-
Tuning is incorrect.
Auto-Tuning did not complete in a pre-set length of
time.
The Auto-Tuning results were not in the applicable
parameter setting range.
Rotational Auto-Tuning was done with a load that
was more than 30% of the rating connected to the
motor.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Possible Solutions
• Make sure that the motor nameplate data entered in Auto-Tuning
is correct.
• Do Auto-Tuning again and correctly set the motor nameplate
data.
Clear the minor fault or alarm and do Auto-Tuning again.
Examine and repair motor wiring.
• Decrease the load.
• Examine the machine area to see if, for example, the motor shaft
is locked.
1.
Stop Auto-Tuning.
2.
Examine the minor fault code and remove the cause of the
problem.
3.
Do Auto-Tuning again.
Possible Solutions
Auto-Tuning did not complete correctly. Do Auto-Tuning again.
Possible Solutions
• Examine and repair motor wiring.
• Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
• Make sure that the input motor nameplate data is correct.
• Do Auto-Tuning again and correctly set the motor nameplate
data.
Possible Solutions
• Examine and repair motor wiring.
• Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
• Make sure that the input motor nameplate data is correct.
• Do Auto-Tuning again and correctly set the motor nameplate
data.
• Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
• If you cannot uncouple the motor and load, make sure that the
load is less than 30% of the motor rating. If a mechanical brake
is installed in the motor, release the brake during Rotational
Auto-Tuning.
Possible Solutions
• Make sure that the input motor nameplate data is correct.
• Do Auto-Tuning again and correctly set the motor nameplate
data.
• Examine and repair the motor wiring.
• If the motor and machine are connected during Rotational Auto-
Tuning, decouple the motor from the machinery.
• Disconnect the machine from the motor and do Rotational Auto-
Tuning again.
• If you cannot uncouple the motor and load, make sure that the
load is less than 30% of the motor rating. If a mechanical brake
is installed in the motor, release the brake during Rotational
Auto-Tuning.

Advertisement

Table of Contents
loading

Table of Contents