YASKAWA HV600 Technical Reference page 655

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
S6-16
EMOVR Customer
Safety Mode
(3247)
S6-17
EMOVR BAS Interlock
Mode
(3248)
S6-20
EMOVR Bypass Fault
ON
(324B)
Expert
S6-23
OV2 Detect Time
(324E)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the status for the customer safety input (when programmed) that must occur for
Emergency Override to function.
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
Sets the status for the BAS Interlock input (when programmed) that must occur for
Emergency Override to function.
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
Enables bypass-specific faults.
0 : FB02
1 : FB03
2 : FB05
3 : FB06
4 : FB07
5 : FB08
6 : FB09
7 : FB10
8 : FB13
9 : FB15
10 : FB16
11 : FB17
12 : FB18
Sets the detection time of ov2 [DC Bus Overvoltage 2] in 0.1 s increments.
Note:
Set this parameter to 0.0 s to disable ov2 detection.
9.14 S: Special Applications
Default
Ref.
(Range)
0
403
(0 - 2)
0
403
(0 - 2)
0
403
(0 - FFFF)
10.0 s
404
(0.0 - 1200.0 s)
9
655