O: Keypad-Related Settings - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.13

o: Keypad-Related Settings

o1: Keypad Display
No.
Name
(Hex.)
o1-03
Frequency Display Unit
Selection
(0502)
o1-05
LCD Contrast
Adjustment
(0504)
RUN
o1-09
Freq. Reference Display
Units
(051C)
o1-10
User Units Maximum
Value
(0520)
o1-11
User Units Decimal
Position
(0521)
o1-13
Freq. Reference Custom
Unit 1
(3105)
o1-14
Freq. Reference Custom
Unit 2
(3106)
o1-15
Freq. Reference Custom
Unit 3
(3107)
o1-18
User Defined Parameter 1 Lets you set values to use as reference information.
(310A)
o1-19
User Defined Parameter 2 Lets you set values to use as reference information.
(310B)
o1-24
Custom Monitor 1
(11AD)
RUN
o1-25
Custom Monitor 2
(11AE)
RUN
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the display units for the frequency reference and output frequency.
0 : 0.01Hz units
1 : 0.01% units
2 : min
-1
(r/min) unit
3 : User Units (o1-09 -o1-11)
Sets the contrast of the LCD display on the keypad.
Sets the unit of display for the frequency reference parameters and frequency-related
monitors when o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-09 ~ o1-
11)].
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
3
5 : m
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(o1-13~15)
50 : None
Sets the value that the drive shows as the maximum output frequency.
Sets the number of decimal places for frequency reference and monitor values.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Sets the first character of the custom unit display when o1-03 = 3 [Frequency Display Unit
Selection = User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom (o1-
13~15)].
Sets the second character of the custom unit display when o1-03 = 3 [Frequency Display
Unit Selection = User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom
(o1-13~15)].
Sets the third character of the custom unit display when o1-03 = 3 [Frequency Display
Unit Selection = User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom
(o1-13~15)].
Sets Custom Monitor 1. You can set a maximum of 12 monitors as user monitors. This
parameter is only available on an HOA keypad.
Sets Custom Monitor 2. You can set a maximum of 12 monitors as user monitors. This
parameter is only available on an HOA keypad.
9.13 o: Keypad-Related Settings
Default
(Range)
0
(0 - 3)
5
(0 - 10)
50
(0 - 50)
Determined by o1-03
(1 - 60000)
Determined by o1-03
(0 - 3)
41
(20 - 7A)
41
(20 - 7A)
41
(20 - 7A)
0
(0 - 999)
0
(0 - 999)
101
(0, 101 - 1299)
102
(0, 101 - 1299)
Ref.
355
356
356
357
357
357
357
358
358
358
9
358
358
641