5.10 o: Keypad-Related Settings
o2-04 Setting
A6
A7
o2-05: Home Mode Freq Ref Entry Mode
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
Name
(Hex.)
o2-06
Keypad Disconnect
Detection
(050A)
If the keypad installed to the drive is disconnected, this parameter will continue to operate.
This parameter is enabled in these conditions:
• b1-02 = 0 [Run Command Selection 1 = Keypad]
• In HAND Mode
0 : Disabled
The drive continues operation if it detects a keypad disconnection.
1 : Enabled
When the drive detects a keypad disconnection, the drive detects oPr [Keypad Connection Fault], and stops
operation. The motor coasts to stop.
o2-09: Region Code
No.
Name
(Hex.)
o2-09
Reserved
(050D)
o2-19: Parameter Write during Uv
No.
Name
(Hex.)
o2-19
Parameter Write during Uv
(061F)
0 : Disabled
1 : Enabled
364
Drive Model
4156
4180
Sets the function that makes it necessary to push
reference value while in Drive Mode.
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
-
Enables and disables the function to change parameter settings during a Uv [DC Bus Undervoltage]
condition.
o2-04 Setting
A8
A9
Description
to use the keypad to change the frequency
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Drive Model
4240
4302
Default
(Setting Range)
0
(0, 1)
and
on the
Default
(Range)
1
(0, 1)
Default
(Range)
-
Default
(Range)
0
(0, 1)