YASKAWA HV600 Technical Reference page 736

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

10.5 Metasys N2 Communications
Object ID
BI 4
Fault Monitor
BI 5
Zero Speed
BI 6
Speed Agree
BI 7
Minor Fault
BI 8
Major Fault
BI 9
Communication Error Monitor
BI 10
Digital Output 7 (TB1 1~3) (Z2-23)
BI 11
Digital Output 8 (TB1 4~6) (Z2-24)
BI 12
Digital Output 9 (TB1 7~9) (Z2-25)
BI 13
Safety Interlock Monitor
BI 14
HAND/AUTO Reference Monitor
BI 15
Digital Input DI-3 Monitor
BI 16
Digital Input DI-4 Monitor
BI 17
Digital Input DI-5 Monitor
BI 18
Digital Input DI-6 Monitor
BI 19
Digital Input DI-7 Monitor
Metasys N2 Binary Output (BO) Summary
Object ID
BO 1
Run Forward Command
BO 2
Run Reverse Command
BO 3
Serial Fault (EFB) Command
BO 4
Fault Reset Command
BO 5
Digital Input 3 (TB2-3) (Z2-03)
BO 6
Digital Input 4 (TB2-4) (Z2-04)
BO 7
Digital Input 5 (TB2-5) (Z2-05)
BO 8
Digital Input 6 (TB2-6) (Z2-06)
BO 9
Digital Input 7 (TB2-7) (Z2-07)
BO10
Panel Lock
BO 11
Communication Fault Enable
*1
When Z3-12 = 0, this input is disabled.
Mailbox Functions
This section defines the Metasys N2 points that read and write parameters.
Reading a Parameter
Two points are defined for reading parameters:
• AO 30 - Specifies the parameter to be read
• AI 38 - Reports the value of the parameter specified in AO 30.
When this point is read, it retrieves data from the parameter and sends it to the controller
Example: Writing a value of 387 (183 hex) to AO 30 specifies parameter b1-04. Reading AI 38 returns the current
setting of parameter b1-04 to the controller.
736
Object Name
Table 10.18 Metasys N2 Binary Output Summary (Drive to Metasys N2)
Object Name
*1
*1
*1
*1
*1
Default
OFF (0) State
0
Not Faulted
0
Not Zero Speed
0
Not Speed Agree
0
No Minor Fault
0
No Major Fault
0
No Error
0
OFF
0
OFF
0
OFF
0
Safety Clear Terminal 3 Closed
0
AUTO or OFF
0
OFF
0
OFF
0
OFF
0
OFF
0
OFF
Default
OFF (0) State
0
Stop
0
Stop
0
No Fault
0
No Reset
0
OFF
0
OFF
0
OFF
0
OFF
0
OFF
0
HAND and OFF Keys Enabled
CE Not Activated if Cable Loss
0
Occurs
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
ON (1) State
Faulted
Zero Speed
Speed Agree
Minor Fault
Major Fault
Error
ON
ON
ON
Safety Set Terminal 3 Open
HAND
ON
ON
ON
ON
ON
ON (1) State
Forward
Reverse
Fault
Reset
ON
ON
ON
ON
ON
HAND and OFF Keys Disabled
CE Activated if Cable Loss Occurs