YASKAWA HV600 Technical Reference page 627

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

H3: Analog Inputs
No.
Name
(Hex.)
H3-01
Terminal A1 Signal Level
Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain Setting Sets the gain of the analog signal input to MFAI terminal A1.
(0411)
RUN
H3-04
Terminal A1 Bias Setting Sets the bias of the analog signal input to MFAI terminal A1.
(0412)
RUN
H3-09
Terminal A2 Signal Level
Select
(0417)
H3-10
Terminal A2 Function
Selection
(0418)
H3-11
Terminal A2 Gain Setting Sets the gain of the analog signal input to MFAI terminal A2.
(0419)
RUN
H3-12
Terminal A2 Bias Setting Sets the bias of the analog signal input to MFAI terminal A2.
(041A)
RUN
H3-13
Analog Input FilterTime
Constant
(041B)
H3-14
Analog Input Terminal
Enable Sel
(041C)
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
H3-42
Mbus Reg 15C3h Input
Function
(0B62)
H3-43
Mbus Reg Inputs
FilterTime Const
(117F)
H3-xx: MFAI Setting Values
Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency
Reference 1
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
Sets the function for MFAI terminal A1.
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
Sets the function for MFAI terminal A2.
Note:
The default setting for H3-10 changes when b5-01 [PID Mode Setting] changes:
• b5-01 = 0 [Disabled]: 0
• b5-01 ≠ 0: B
Sets the time constant for primary delay filters on MFAI terminals.
Sets which terminal or terminals to enable when H1-xx = C [MFDI Function Selection =
Analog Terminal Enable Selection] is activated.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to
change this setting.
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to
change this setting.
Sets the MEMOBUS AI1 function.
Sets the MEMOBUS AI2 function.
Sets the MEMOBUS AI3 function.
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input
register values.
The input value from the MFAI terminal set with this function becomes the master frequency reference.
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference
1) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is
a setting value of 100%.
9.10 H: Terminal Functions
Description
Default
Ref.
(Range)
0
295
(0 - 3)
0
295
(0 - 31)
100.0%
295
(-999.9 - +999.9%)
0.0%
296
(-999.9 - +999.9%)
2
296
(0 - 3)
Determined by b5-01
296
(0 - 31)
100.0%
296
(-999.9 - +999.9%)
0.0%
297
(-999.9 - +999.9%)
0.03 s
297
(0.00 - 2.00 s)
2
297
(1 - 3)
0
297
(-500 - +500)
0
297
(-500 - +500)
F
298
(4 - 2E)
F
298
(4 - 2E)
F
298
(4 - 2E)
0.00 s
298
(0.00 - 2.00 s)
Ref.
298
298
299
627
9