6.5 Faults
Code
Name
CPF06
EEPROM Memory Data Error
Note:
• The drive detects this error if there is an error in the data written to the EEPROM of the drive.
• Do a Fault Reset to clear the fault.
• Fault trace is not available for this fault.
Code
Name
CPF07
Terminal Board Connection Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF08
Terminal Board Connection Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF11
RAM Fault
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF12
FLASH Memory Fault
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF13
Watchdog Circuit Exception
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF14
Control Circuit Fault
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
474
Causes
The drive power supply was de-energized while a
communication option card entered a parameter Write
command.
An EEPROM peripheral circuit error occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Possible Solutions
Set A1-03 = 2220 [Initialize Parameters = 2-Wire Initialization]
and initialize the drive.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.