Advertisement

5.13

Y: Application Features

Y1: Application Basics

Y1-04: Sleep Wake-up Level
No.
Name
(Hex.)
Y1-04
Sleep Wake-up Level
(3C03)
RUN
Note:
• When PID operates in reverse mode, the feedback value must increase to more than the start level for the time set in Y1-05 for the system to
start.
• When Y2-01 = 5 [Sleep Level Type = Output Frequency (non-PID)], the drive will ignore this parameter.
• Set this parameter to 0.0 to disable the function.
• Range is 0.00 to 99.99 with sign-bit "-" or "+" indicating Delta to Setpoint.
• Display unit and scaling change when the system units change.
Y1-05: Sleep Wake-up Level Delay Time
No.
Name
(Hex.)
Y1-05
Sleep Wake-up Level Delay
Time
(3C04)
RUN
Y1-06: Minimum Speed
No.
Name
(Hex.)
Y1-06
Minimum Speed
(3C05)
RUN
Note:
The unit, decimal place, and setting range change when the Y1-07 [Minimum Speed Units] setting changes:
• Y1-07 = 0 [Hz]: The setting range is 0.0 Hz to E1-04 Hz.
• Y1-07 = 1 [RPM]: The setting range is 0 RPM to (E1-04 × 60) RPM.
Y1-07: Minimum Speed Units
No.
Name
(Hex.)
Y1-07
Minimum Speed Units
(3C06)
0 : Hz
1 : RPM
Note:
Changing Y1-07 will set Y1-06 [Minimum Speed] to the default value.
Y1-08: Low Feedback Level
No.
Name
(Hex.)
Y1-08
Low Feedback Level
(3C07)
RUN
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the level that feedback must be less than for the time set in Y1-05 [Sleep Wake-up Level Delay
Time] to start the system. This level also sets the wake up level when the drive is in Sleep Mode.
When Y1-04 < 0, the feedback level must decrease this amount to less than the setpoint.
Sets the drive to start the System again when the feedback decreases to less than Y1-04 [Sleep Wake-
up Level] for the time set in this parameter.
Sets the minimum frequency at which the drive will run. The drive applies this setting to HAND and
AUTO modes.
Sets the units and decimal place for Y1-06 [Minimum Speed].
Sets the lower detection level for the PID feedback.

5.13 Y: Application Features

Description
Description
Description
Description
Description
Default
(Range)
0.0
(-999.9 - +999.9)
Default
(Range)
1 s
(0 - 3600 s)
Default
(Range)
0.0 Hz
Determined by Y1-07
Default
5
(Range)
0
(0, 1)
Default
(Range)
0.00%
(0.00 - 99.99%)
407