5.7 H: Terminal Functions
H3-04: Terminal A1 Bias Setting
No.
Name
(Hex.)
H3-04
Terminal A1 Bias Setting
(0412)
RUN
This parameter sets the bias for the function set for terminal A1 as a percentage when 0 V (4 mA or 0 mA) is input.
Use this parameter and H3-03 [Terminal A1 Gain Setting] to adjust the characteristics of the analog input signal to
terminal A1.
H3-09: Terminal A2 Signal Level Select
No.
Name
(Hex.)
H3-09
Terminal A2 Signal Level
Select
(0417)
0 : 0-10V (LowLim=0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due
to gain and bias settings will be read as 0%.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal due to
gain and bias settings will be read as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal due to
gain and bias settings will be read as 0%.
Note:
When H3-09 = 0, set Jumper switch S1 to the V side (voltage). When H3-09 = 2, 3, set Jumper switch S1 to the I side (current). The default
setting is the I side (current).
H3-10: Terminal A2 Function Selection
No.
Name
(Hex.)
H3-10
Terminal A2 Function
Selection
(0418)
Note:
The default setting for H3-10 changes when b5-01 [PID Mode Setting] changes:
• b5-01 = 0 [Disabled]: 0
• b5-01 ≠ 0: B
H3-11: Terminal A2 Gain Setting
No.
Name
(Hex.)
H3-11
Terminal A2 Gain Setting
(0419)
RUN
When 10 V (or 20 mA) is input, this parameter sets the reference quantity for the function set for terminal A2 as a
percentage.
Use this parameter and H3-12 [Terminal A2 Bias Setting] to adjust the characteristics of the analog input signal to
terminal A2.
296
Sets the bias of the analog signal input to MFAI terminal A1.
Sets the input signal level for MFAI terminal A2.
Sets the function for MFAI terminal A2.
Sets the gain of the analog signal input to MFAI terminal A2.
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
2
(0 - 3)
Default
(Range)
Determined by b5-01
(0 - 31)
Default
(Range)
100.0%
(-999.9 - +999.9%)