9.9

F: Options

F6: Communication Options
No.
Name
(Hex.)
F6-01
Communication Error
Selection
(03A2)
F6-02
Comm External Fault
(EF0) Detect
(03A3)
F6-04
bUS Error Detection
Time
(03A5)
F6-08
Comm Parameter Reset
@Initialize
(036A)
F6-14
BUS Error Auto Reset
(03BB)
F6-15
Comm. Option
Parameters Reload
(0B5B)
F7: Ethernet Options
No.
Name
(Hex.)
F7-01
IP Address 1
(03E5)
F7-02
IP Address 2
(03E6)
F7-03
IP Address 3
(03E7)
F7-04
IP Address 4
(03E8)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the method to stop the motor or let the motor continue operating when the drive
detects bUS [Option Communication Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
Sets the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized
with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Sets the automatic reset function for bUS [Option Communication Errors].
0 : Disabled
1 : Enabled
Sets the update method when you change F6-xx, F7-xx [Communication Options].
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
Description
Sets the first octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
Sets the second octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
Sets the third octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
Sets the fourth octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
9.9 F: Options
Default
Ref.
(Range)
1
253
(0 - 5)
0
254
(0, 1)
2.0 s
254
(0.0 - 5.0 s)
0
255
(0, 1)
0
255
(0, 1)
0
255
(0 - 2)
Default
Ref.
(Range)
192
255
(0 - 255)
168
255
(0 - 255)
1
256
(0 - 255)
20
256
(0 - 255)
611