5.7 H: Terminal Functions
■
10: Alarm
Setting Value
Function
10
Alarm
■
11: Fault Reset Command Active
Setting Value
Function
11
Fault Reset Command
Active
■
12: Timer Output
Setting Value
Function
12
Timer Output
Note:
Refer to
Timer Function Operation on page 206
■
13: Speed Agree 2
Setting Value
Function
13
Speed Agree 2
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
L4-04: Speed Agree Detection Width(+/-)
■
14: User-Set Speed Agree 2
Setting Value
Function
14
User-Set Speed Agree 2
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ±
L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency
reference ± L4-04.
284
The terminal activates when the drive detects a minor fault.
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
Use this setting when the drive uses the timer function as an output terminal.
for more information.
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width
(+/-)].
Figure 5.52 Speed Agree 2 Time Chart
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed
Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Description
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference