YASKAWA HV600 Technical Reference page 573

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Remove the Cooling Fans
1.
Push the tabs on the left and right sides of the fan finger guard and pull up to remove the fan finger guard from
the drive.
A - Fan finger guard
2.
Pull the cooling fans straight up from the drive. Remove the protective tubes on the power supply connectors
and disconnect the connectors to remove the fans from the drive.
A - Cooling fan
Install the Cooling Fans
Reverse the removal procedure to install the cooling fans.
1.
Connect the drive and the fan connectors, and attach the protective tubes.
A - Protective tube
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
8.4 Replace Drive Cooling Fans and Circulation Fans
Figure 8.27 Remove the Fan Finger Guard
B - Protective tube
Figure 8.28 Remove the Cooling Fans
Figure 8.29 Connect the Power Supply Connectors
8