Section 6 Wide Area Measurement System; Protocol Reporting Via Ieee 1344 And C37.118 Pmureport; Identification; Application - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
Section 6
6.1
6.1.1
6.1.2
Phasor measurement unit RES670 2.2 IEC
Application manual
Wide area measurement system
Protocol reporting via IEEE 1344 and C37.118
PMUREPORT

Identification

Function description
Protocol reporting via IEEE 1344 and
C37.118

Application

The phasor measurement reporting block moves the phasor calculations into an
IEEE C37.118 and/or IEEE 1344 synchrophasor frame format. The PMUREPORT
block contains parameters for PMU performance class and reporting rate, the
IDCODE and Global PMU ID, format of the data streamed through the protocol,
the type of reported synchrophasors, as well as settings for reporting analog and
digital signals.
The message generated by the PMUREPORT function block is set in accordance
with the IEEE C37.118 and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero
sequence in case of 3-phase phasor and L1, L2 or L3 in case of single phase
phasor), PMU's Service class (Protection or Measurement), Phasor representation
(polar or rectangular) and the data types for phasor data, analog data and frequency
data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP
group clients for multicast or unicast transmission of phasor data from the IED.
More information regarding synchrophasor communication structure and
TCP/UDP configuration is available in section
Streaming Protocol
Configuration.
Multiple PMU functionality can be configured in the IED, which can stream out
same or different data at different reporting rates or different performance (service)
classes. There are 2 instances of PMU functionality available in the IED. Each
instance of PMU functionality includes a set of PMU reporting function blocks
tagged by the same instance number (1 or 2). As shown in the following figures,
each set of PMU reporting function blocks includes PMUREPORT,
Wide area measurement system
IEC 61850
IEC 60617
identification
identification
PMUREPORT
-
C37.118 Phasor Measurement Data
Section 6
GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v1
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
ANSI/IEEE C37.2
device number
-
GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4
87