1MRK 505 363-UEN A
Section 6
6.1
Low impedance restricted earth fault protection
REFPDIF
6.1.1
Identification
Function description
Restricted earth-fault protection,
low impedance
6.1.2
Application
A breakdown of the insulation between a transformer winding and the core or the tank may
result in a large fault current which causes severe damage to the windings and the transformer
core. A high gas pressure may develop, damaging the transformer tank.
Fast and sensitive detection of earth faults in a power transformer winding can be obtained in
solidly earthed or low impedance earthed networks by the restricted earth-fault protection.
The only requirement is that the power transformer winding is connected to earth in the star
point (in case of star-connected windings) or through a separate earthing transformer (in case
of delta-connected windings).
The low impedance restricted earth-fault protection REFPDIF is a winding protection function.
It protects the power transformer winding against faults involving earth. Observe that single
phase-to-earth faults are the most common fault types in transformers. A sensitive earth-fault
protection is therefore desirable.
A restricted earth-fault protection is the fastest and the most sensitive protection, a power
transformer winding can have and will detect faults such as:
•
earth faults in the transformer winding when the network is earthed through an
impedance
•
earth faults in the transformer winding in solidly earthed network when the point of the
fault is close to the winding star point.
The restricted earth-fault protection is not affected, as a differential protection, with the
following power transformer related phenomena:
•
magnetizing inrush currents
•
overexcitation magnetizing currents
•
load tap changer
•
external and internal phase faults which do not involve earth
•
symmetrical overload conditions
Application manual
Differential protection
IEC 61850
identification
REFPDIF
IEC 60617
ANSI/IEEE C37.2
identification
device number
87N
IdN/I