Differential Protection; Low Impedance Restricted Earth Fault Protection Refpdif; Identification; Application - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
Section 6
6.1
Low impedance restricted earth fault protection
REFPDIF
6.1.1

Identification

Function description
Restricted earth-fault protection,
low impedance
6.1.2

Application

A breakdown of the insulation between a transformer winding and the core or the tank may
result in a large fault current which causes severe damage to the windings and the transformer
core. A high gas pressure may develop, damaging the transformer tank.
Fast and sensitive detection of earth faults in a power transformer winding can be obtained in
solidly earthed or low impedance earthed networks by the restricted earth-fault protection.
The only requirement is that the power transformer winding is connected to earth in the star
point (in case of star-connected windings) or through a separate earthing transformer (in case
of delta-connected windings).
The low impedance restricted earth-fault protection REFPDIF is a winding protection function.
It protects the power transformer winding against faults involving earth. Observe that single
phase-to-earth faults are the most common fault types in transformers. A sensitive earth-fault
protection is therefore desirable.
A restricted earth-fault protection is the fastest and the most sensitive protection, a power
transformer winding can have and will detect faults such as:
earth faults in the transformer winding when the network is earthed through an
impedance
earth faults in the transformer winding in solidly earthed network when the point of the
fault is close to the winding star point.
The restricted earth-fault protection is not affected, as a differential protection, with the
following power transformer related phenomena:
magnetizing inrush currents
overexcitation magnetizing currents
load tap changer
external and internal phase faults which do not involve earth
symmetrical overload conditions
Application manual

Differential protection

IEC 61850
identification
REFPDIF
IEC 60617
ANSI/IEEE C37.2
identification
device number
87N
IdN/I
SYMBOL-AA V1 EN-US
Section 6
Differential protection
IP14640-1 v6
M14843-1 v5
IP14941-1 v1
M13940-3 v11
67