7-4 AC / DC Reactor

AC Input Reactor
Installing an AC reactor on the input side of an AC motor drive can increase line impedance, improve
the power factor, reduce input current, and reduce interference generated from the motor drive. It also
reduces momentary voltage surges or abnormal current spikes. For example, when the main power
capacity is higher than 500 kVA, or when using a switching capacitor bank, momentary voltage and
current spikes may damage the AC motor drive's internal circuit. An AC reactor on the input side of the AC
motor drive protects it by suppressing surges.
Installation
Install an AC input reactor in series with the main power to the three input phases R S T as shown
below:
Following table shows the standard AC reactors specification of Delta CP2000
200V–230V, 50 / 60 Hz
Model
kW
0.75
VFD007CP23A-21
VFD015CP23A-21
1.5
VFD022CP23A-21
2.2
3.7
VFD037CP23A-21
5.5
VFD055CP23A-21
VFD075CP23A-21
7.5
VFD110CP23A-21
11
15
VFD150CP23A-21
18.5 25
VFD185CP23A-21
22
VFD220CP23A-21
VFD300CP23A-21
30
VFD370CP23A-00/-21
37
45
VFD450CP23A-00/-21
55
VFD550CP23A-00/-21
VFD750CP23A-00/-21
75
VFD900CP23A-00/-21
90
Wiring of AC input reactor
Rated Amps
Max.
of AC Reactor
continuous
(Arms)
Amps (Arms)
HP
Normal
Light
Normal
Duty
Duty
Duty
1
4.6
5
7.36
2
5
7.5
8
3
8
10
12.8
5
11
15
17.6
7.5
17
21
27.2
10
25
31
40
15
33
46
52.8
20
49
61
78.4
65
75
104
30
75
90
120
40
90
105
144
50
120
146
192
60
146
180
233.6
75
180
215
288
100
215
276
344
125
255
322
408
Chapter 7 Optional AccessoriesCP2000
3%
Impedance
Impedance
(mH)
Light
Normal
Light
Normal
Duty
Duty
Duty
Duty
6
2.536
2.536
4.227
9
2.536
1.585
4.227
12
1.585
1.152
2.642
18
1.152
0.746
1.92
25.2
0.746
0.507
1.243
37.2
0.507
0.38
0.845
55.2
0.38
0.26
0.633
73.2
0.26
0.196
0.433
90
0.196
0.169
0.327
108
0.169
0.141
0.282
126
0.141
0.12
0.235
175.2
0.12
0.087
0.2
216
0.087
0.07
0.145
258
0.07
0.059
0.117
331.2
0.059
0.049
0.098
386.4
0.049
0.037
0.082
7-13
Figure 7-6
5%
Input AC reactor
Built-in
(mH)
Delta part #
DC
reactor
Light
Normal
Duty
Duty
DR005A0254 DR005A0254
4.227
No
DR005A0254 DR008A0159
2.642
No
DR008A0159 DR011A0115
1.92
No
DR011A0115 DR017AP746
1.243
No
DR017AP746 DR025AP507
0.845
No
DR025AP507 DR033AP320
0.633
No
DR033AP320 DR049AP215
0.433
No
0.327
No
DR049AP215 DR065AP162
0.282
No
DR065AP162 DR075AP170
DR075AP170 DR090AP141
0.235
No
DR090AP141 DR105AP106
0.2
No
DR105AP106 DR146AP087
0.145
Yes
DR146AP087 DR180AP070
0.117
Yes
DR180AP070 DR215AP059
0.098
Yes
DR215AP059 DR276AP049
0.082
Yes
DR276AP049 DR346AP037
0.062
Yes
3%
Light
Duty
Table 7-19