Ac / Dc Reactor - Delta C2000 Series User Manual

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 7 Optional AccessoriesC2000

7-4 AC / DC Reactor

AC Input Reactor
Installing an AC reactor on the input side of an AC motor drive can increase line impedance, improve
the power factor, reduce input current, and reduce interference generated from the motor drive. It also
reduces momentary voltage surges or abnormal current spikes. For example, when the main power
capacity is higher than 500 kVA, or when using a switching capacitor bank, momentary voltage and current
spikes may damage the AC motor drive's internal circuit. An AC reactor on the input side of the AC motor
drive protects it by suppressing surges.
Installation
Install an AC input reactor in series with the main power to the three input phases R S T as shown
below:
Following table shows the standard AC reactors specification of Delta C2000
200V~230V/ 50~60Hz
Model
HP
1
VFD007C23A
2
VFD015C23A
3
VFD022C23A
5
VFD037C23A
7.5
VFD055C23A
10
VFD075C23A
15
VFD110C23A
20
VFD150C23A
25
VFD185C23A
30
VFD220C23A
40
VFD300C23A
50
VFD370C23A
60
VFD450C23A
75
VFD550C23A
100
VFD750C23A
125
VFD900C23A
Wiring of AC input reactor
Rated Current
Saturation current
(Arms)
(Arms)
5
8.64
8
12.78
11
18
17
28.8
25
43.2
33
55.8
49
84.6
65
111.6
75
127.8
90
154.8
120
205.2
146
250.2
180
307.8
215
367.2
255
435.6
346
592.2
3%
5%
impedance
impedance
(mH)
(mH)
2.536
4.227
1.585
2.642
1.152
1.922
0.746
1.243
0.507
0.845
0.32
0.534
0.216
0.359
0.163
0.271
0.169
0.282
0.141
0.235
0.106
0.176
0.087
0.145
0.070
0.117
0.059
0.098
0.049
0.083
0.037
0.061
7-10
Figure 7-6
Built-in
Input AC reactor
DC reactor
Delta part #
No
DR005A0254
No
DR008A0159
No
DR011A0115
No
DR017AP746
No
DR025AP507
No
DR033AP320
No
DR049AP215
No
DR065AP163
No
DR075AP170
No
DR090AP141
Yes
DR146AP087
Yes
DR146AP087
Yes
DR180AP070
Yes
DR215AP059
Yes
DR276AP049
Yes
DR349AP037
Table 7-15