Non-Fuse Circuit Breaker Chart; Fuse Specification Chart; Appendix B Accessories; Reactor - Delta VFD-EL-W Series User Manual

Sensorless vector control compact drive
Hide thumbs Also See for VFD-EL-W Series:
Table of Contents

Advertisement

B.1 Non-fuse Circuit Breaker Chart
For one-phase/three-phase drives, the current rating of the breaker must be between 2–4 times the rated input
current.
Model
VFD002EL21W
VFD004EL21W
VFD007EL21W
VFD015EL21W
VFD022EL21W

Fuse Specification Chart

Fuse specifications lower than the table below are allowed.
Model
VFD002EL21W
VFD004EL21W
VFD004EL43W
VFD007EL21W
VFD007EL43W
VFD015EL21W
VFD015EL43W
VFD022EL21W
VFD022EL43W
VFD040EL43W
B.1 Non-fuse Circuit Breaker Chart
B.2 Reactor
B.2.1 AC Reactor
B.2.2 Zero Phase Reactor
B.3 Digital Keypad
B.3.1 PU06
B.3.2 PU08 and PU08V
B.4 Optional Cooling Fan
One-phase
Recommended
non-fuse breaker (A)
10
15
20
30
50
I (A)
Input
4.9
6.5
1,8
9.3
3.2
15.7
4.3
24.0
7.1
10.0
Model
VFD004EL43W
VFD007EL43W
VFD015EL43W
VFD022EL43W
VFD040EL43W
I (A)
Output
1.6
2.5
1,.5
4.2
2.5
7.5
4.2
11.0
5.5
9.0

Appendix B Accessories

Three-phase
non-fuse breaker (A)
Line Fuse
I (A)
10
15
5
20
5
30
10
50
15
20
Recommended
5
5
10
15
20
Bussmann P/N
JJN-10
JJN-15
JJS-6
JJN-20
JJS-6
JJN-30
JJS-10
JJN-50
JJS-15
JJS-20
B-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents