Source Of First Master Frequency Command; Source Of Second Master Frequency Command; Source Of First Operation Command - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-B Series
Group 2: Operation Method Parameters
02 - 00

Source of First Master Frequency Command

Settings
02 - 13

Source of Second Master Frequency Command

Settings
These parameters set the Master Frequency Command Source of the AC motor drive.
02 - 01

Source of First Operation Command

Settings
5-34
00
Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
05
RS-485 serial communication (RJ-11). Last used frequency not
saved.
06
Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
00
Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN.
Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
05
RS-485 serial communication (RJ-11). Last used frequency not
saved.
06
Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
00
Digital keypad (PU01)
01
External terminals. Keypad STOP/RESET enabled.
02
External terminals. Keypad STOP/RESET disabled.
03
RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04
RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Revision July 2008, BE16, SW V4.08 & V5.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents