Control Circuit Wiring - Delta VFD-A Series User Manual

High-performance/low-noise general-purpose ac motor drives 230v/460v / 3-phase 0.75 - 22kw 1-30hp
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales

Control Circuit Wiring

(1) Control terminal block designations
The control leads must be routed separately from the power supply and motor leads.
They must not be fed through the same cable conduit.
220V/440V Class 1∼5HP (AWG: 28 – 14; Torque:4 kgf-cm)
220V/440V Class 7.5∼30HP (AWG: 24 – 12; Torque:4 kgf-cm)
RA
RB
(2) Control terminal block descriptions
Close Contacts
between Terminals
RA - RC
RB - RC
MI1 - DCM
MI2 - DCM
MI3 - DCM
REV - DCM
FWD - DCM
RST - DCM
EF - DCM
DFM - DCM
TRG - DCM
MO1 - MCM
MO2 - MCM
+10V - ACM
AVI - ACM
ACI - ACM
AFM - ACM
SG+ - SG-
+EV - DCM
Note: Use twisted-shielded or twisted-pair shielded-lead wires for the control signal.
recommended to run signal wiring in a separate steel conduit.
connected at the drive.
Call 1(800)985-6929 for Sales
deltaacdrives.com
Terminal Symbol
RA
RB
RC
+10V
MI3
FWD
REV
MI1
MI2
RC
MI1
MI2 MI3
REV FWD
RST
Terminals Use
Multi-function indication output
contact
Multi-function indication output
contact
Multi-function input 1
Multi-function input 2
Multi-function input 3
Reverse / Stop
Forward / Stop
Reset
External fault
Digital frequency meter
Counter trigger input
Multi-function PHC output 1
Multi-function PHC output 2
Power supply for speed setting +10 V (20 mA max. output current)
Analog voltage input
Analog current input
Analog frequency/current
meter
Serial communication interface RS-485 serial port
Auxiliary control power source
deltaacdrives.com
AVI
ACI
AFM
ACM
MO1
MO2
RST
EF
TRG
DCM
DFM
SG+
+10V
EF
TRG
DFM
DCM
MO1
MO2
MCM
Function
Refer to Chapter 5, Pr.57
Refer to Chapter 5, Pr.39, 40, 41
"Open"→stop, "Close" → Reverse
"Open"→stop, "Close" → Forward
"Close" → Reset
"Close" → External fault
Digital frequency output (0, +10 V)
"Open"→"Close":(counter value)+1
Refer to Pr.45, 46
(open collector output)
0 ∼10 V (Max. output freq.) input
4 ∼20 mA (Max. output freq.) input
0 ∼10 V (Max. output freq.) output
DC 20V ~ 24V (50mA Max.)
The shield wire should only be
9
sales@deltaacdrives.com
MCM
+EV
SG-
DCM
AFM
XX
AVI
ACI
ACM
SG+
SG
sales@deltaacdrives.com
It is

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents