A35802 (F, N)
TM: Time slice overflow
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
A time slice overflow has occurred on the Terminal Module.
Remedy:
Replace the Terminal Module.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35803 (F, N)
TM: Memory test
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred during the memory test on the Terminal Module.
Remedy:
- check whether the permissible ambient temperature for the Terminal Module is being maintained.
- replace the Terminal Module.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35804 (N, A)
TM: CRC
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A checksum error has occurred when reading-out the program memory on the Terminal Module.
Fault value (r0949, interpret hexadecimal):
Difference between the checksum at POWER ON and the actual checksum.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Terminal Module.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A35805 (F, N)
TM: EEPROM checksum error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
Internal parameter data is corrupted.
Alarm value (r2124, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Terminal Module 31 (TM31).