1MRS758335 B
3.4.3.2
REU611
Application Manual
Functional diagrams for disturbance recorder and trip circuit
supervision
PHPTOV1_OPERATE
PHPTOV2_OPERATE
OR
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE
OR
PHPTUV3_OPERATE
ROVPTOV1_OPERATE
OR
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
PSPTUV1_OPERATE
PSPTUV2_OPERATE
OR
NSPTOV1_OPERATE
NSPTOV2_OPERATE
FRPFRQ1_OPERATE
OR
FRPFRQ2_OPERATE
GUID-E2B78222-723F-42A9-9F6C-1AE1E3BCDF9F V1 EN
Figure 20:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. The active setting group is also to be recorded via
SG_1_ACT to SG_6_ACT. The disturbance recorder triggered signal indication is
connected to LED 6.
Table 15:
Disturbance recorder binary channel default value
Channel number
Binary channel 1
Binary channel 2
Binary channel 3
Binary channel 4
Binary channel 5
Binary channel 6
Binary channel 7
Binary channel 8
Binary channel 9
Binary channel 10
Binary channel 11
Binary channel 12
Table continues on next page
REU611 standardized configuration
DISTURBANCE RECORDER
RDRE1
PHPTOV1_START
C1
PHPTOV2_START
C2
PHPTOV3_START
C3
PHPTUV1_START
C4
PHPTUV2_START
C5
PHPTUV3_START
C6
PSPTUV1_START
C7
PSPTUV2_START
C8
NSPTOV1_START
C9
NSPTOV2_START
C10
ROVPTOV1_START
C11
ROVPTOV2_START
C12
ROVPTOV3_START
C13
FRPFRQ1_START
C14
FRPFRQ2_START
C15
C16
TRIGGERED
C17
C18
C19
C20
SEL1_Blocking 1
C21
SEL1_CB Closed
C22
SEL1_CB_Open
C23
SEL1_External_Trip
C24
SG_1_ACT
C25
SG_2_ACT
C26
SG_3_ACT
C27
SG_4_ACT
C28
SG_5_ACT
C29
SG_6_ACT
C30
BUS_VT_MCB_OPEN
C31
Channel ID text
PHPTOV1_START
PHPTOV2_START
PHPTOV3_START
PHPTUV1_START
PHPTUV2_START
PHPTUV3_START
PSPTUV1_START
PSPTUV2_START
NSPTOV1_START
NSPTOV2_START
ROVPTOV1_START
ROVPTOV2_START
Section 3
OSWGAPC11
SELGAPC4
IN_1
IN_12
OUT_6
OUT
Level trigger mode
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
LED 6