Records Menu; Fault Summary; Figure 7-1 Fault Summary Record - ABB DPU 1500R Instruction Book

Distribution protection unit
Table of Contents

Advertisement

9/99
Records

Fault Summary

The DPU1500R provides a summary of the last 32 faults. The Fault Summary includes the:
Record number (most recent listed first as "1")
Fault number (numbered in order occurred)
Enabled settings table and recloser sequence number (1, 2, 3, 4 or L for lockout)
Tripping element
Date and time
Phase and neutral currents (magnitude only)
After a fault, the MMI continuously displays the apparent distance to the fault in miles and the fault currents (magnitude
only) until the targets are reset. Save the Fault Summary as a file via WinECP.
Records

Records Menu

The DPU1500R provides fault and operations records. It also provides a
list of records not yet reported.
Figure 7-1. Fault Summary Record
website:www.abb.com/papd
ABB Distribution Protection Unit 1500R
7-1