High-Function Pid Parameters - Delta CFP2000 Series User Manual

Ip55 fan and pump drive
Table of Contents

Advertisement

08 High-function PID Parameters

Pr.
Parameter Name
Terminal selection of PID
08-00
feedback
08-01
Proportional gain (P)
08-02
Integral time (I)
08-03
Differential time (D)
08-04
Upper limit of integral control
08-05
PID output command limit
PID feedback value by
08-06
communication protocol
08-07
PID delay time
08-08
Feedback signal detection time
08-09
Feedback signal fault treatment
08-10
Sleep frequency
08-11
Wake-up frequency
08-12
Sleep time
08-13
PID deviation level
08-14
PID deviation time
08-15
PID feedback filter time
08-16
PID compensation selection
08-17
PID compensation
08-18
Sleep mode function setting
08-19
Wake-up integral limit
08-20
PID mode selection
Enable PID to change the
08-21
operation direction
08-22
Wake-up delay time
Chapter 11 Summary of Parameter SettingsCFP2000
Setting Range
0: No function
1: Negative PID feedback by analog input
(Pr.03-00–03-02)
4: Positive PID feedback by analog input
(Pr.03-00–03-02)
0.0–100.0
0.00–100.00 sec.
0.00: No integral
0.00–1.00 sec.
0.0–100.0%
0.0–110.0%
-200.00–200.00%
0.0–35.0 sec.
0.0–3600.0 sec.
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
0.00–599.00 Hz or 0–200.00%
0.00–599.00 Hz or 0–200.00%
0.0–6000.0 sec.
1.0–50.0%
0.1–300.0 sec.
0.1–300.0 sec.
0: Parameter setting (Pr.08-17)
1: Analog input
-100.0–100.0%
0: Refer to PID output command
1: Refer to PID feedback signal
0.0–200.0%
0: Serial connection
1: Parallel connection
0: Operation direction cannot be changed
1: Operation direction can be changed
0.00–600.00 sec.
11-29
Default
0
1.0
1.00
0.00
100.0
100.0
Read
only
0.0
0.0
0
0.00
0.00
0.0
10.0
5.0
5.0
0
0.0
0
50.0
0
0
0.00