High-Function Pid Parameters - Delta CP2000 Series User Manual

Sensorless fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCP2000

08 High-function PID Parameters

Terminal Selection of PID Feedback
Settings
 Pr.08-00≠0 enables the PID function.
 Negative feedback means:
+target value – feedback. The detection value increases by increasing the output frequency.
 Positive feedback means:
-target value + feedback. The detection value decreases by increasing the output frequency.
 When Pr.08-00≠7 neither ≠8, the input value is disabled. The value of the setting does not
remain the same after the drive is OFF.
 Related applicable parameters: Pr.00-20, Pr.03-00–03-02
When enable the PID function (Pr.08-00 ≠ 0), if Pr.00-20 is set to 2 "External analog input",
Pr.03-00–03-02 need to be set to 4 "PID target value" accordingly.
Master Frequency Command (AUTO) Source / Source Selection of the PID Target
Settings
0: No function
1: Negative PID feedback: by analog input (Pr.03-00–03-02)
4: Positive PID feedback: by analog input (Pr.03-00–03-02)
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Refer to Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (does not include CANopen card)
12.1-08-1
 This parameter can be set during operation.
Default: 0
Default: 0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vfd007cp23a-21Vfd015cp23a-21Vfd022cp23a-21Vfd037cp23a-21Vfd055cp23a-21Vfd007cp43a-21 ... Show all

Table of Contents