Chapter 12 Description of Parameter Settings
12-1 Description of parameter settings
00 Drive Parameters
Identity Code of the AC Motor Drive
Settings Read Only
Display AC Motor Drive Rated Current
Settings Read Only
 Pr. 00-00 displays the identity code of the AC motor drive. Using the following table to check if
Pr.00-01 setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the identity
code Pr.00-01.
 The factory setting is the rated current for normal duty. Please set Pr.00-16 to 1 to display the rated
current for the heavy duty.
Frame
kW
Pr.00-00
Rated Current for
Heavy Duty
Rated Current for
Light Duty
Parameter Reset
Settings 0: No Function
 When it is set to 1, all parameters are read only except Pr.00-02~00-08 and it can be used with
password setting for password protection. It needs to set Pr.00-02 to 0 before changing other
parameter settings.
 When it is set to 9 or 10: all parameters are reset to factory settings. If password is set in Pr.00-08,
input the password set in Pr.00-07 to reset to factory settings.
 When it is set to 5, KWH display value can be reset to 0 even when the drive is operating. Pr.
05-26, 05-27, 05-28, 05-29, 05-30 reset to 0.
 When it is set to 6: clear internal PLC program (includes the related settings of PLC internal
CANopen master)
 When it is set to 7: reset the related settings of CANopen slave.
Chapter 12 Description of Parameter SettingsCT2000 Series
B
11
15
18.5
22
410
411
412
413
17
23
30
36
22.5
30
36
45
1: Write protection for parameters
5:
Reset KWH display to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
9: All parameters are reset to factory settings(base frequency is 50Hz)
10: All parameters are reset to factory settings (base frequency is 60Hz)
12.1-00-1
 This parameter can be set during operation.
460V series
C
30
37
37
414
415
415
43
57
57
56
72
72
Factory Setting: #.#
Factory Setting: #.#
D0
D
45
55
55
75
416
417
417
418
69
86
86
105
91
110
110
144
Factory Setting: 0
90
419
143
180

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents