Special Parameters (07) group

Setting up these parameters is optional but useful to minimize efforts to correct drive faults.
Parameter
Display Text
07-06 Restart
Momentary
after momentary
Power
power down
07-07 Maximum
Power Loss
power loss
Time
duration
07-10 Restart
Fault Re-RUN
after fault
Way
07-11 Number of
Auto Restart
auto restarts
3-5 Setting Up Parameters for the First Time | CP2000
Description of Parameter
The operation mode when
the AC motor drive restarts
from a
momentary power loss.
Parameter options:
0 – Stop operation
1 – Speed search start, at
the current speed
2 – Speed search start, at
minimum frequency
The duration of the period of
power loss in seconds
before the drive will stop
operation.
Range is between 2 to 20
seconds.
This determines what the
drive does after a fault
occurs.
Parameter options:
0 – Stop operation
1 – Restarts automatically,
speed search starts with
current speed
2- Restarts automatically,
speed search starts with
minimum frequency
The number of times the
drive can restart
automatically after a fault.
Range is 0 to 10 times.
11
Default
Preferred
Value
Value
0
1
2 secs
20 secs
0
1
0
1 or more