Section 3 Programming

3-2-2 Setting parameters

(1) Analog input unit (Target type: NA0AX06-MR, NA0AW06-MR, NA3AW03-MR)
For an analog input unit, set the resolution and moving average execution times.
Parameter
Resolution
Moving average execution times
* What does the "14 bits (12 bits)" of the resolution mean?
This means the resolution is 14 bits, however, the lower two bits are fixed to 0. The A/D conversion value range is the same as
for 14 bits as shown below, however, the value increments or decrements by 4.
UNIPOLAR: 0 to 16000, BIPOLAR: -8000 to 8000
<How to set parameters>
1) Right-click the analog unit registered in the system definition screen and left-click [Properties]. The "Module properties" dialog
box opens.
Setting range
14 bits, 12 bits, or 14 bits (12 bits) *
1 (No moving average) to 16 times
3-5
* The setting procedure is the same for
a front board type unit.