Section 3
Analog inputs
Definition of direction
for directional functions
Reverse
Set parameter
CT_WyePoint
Correct Setting is
"ToObject"
ANSI05000456 V1 EN-US
Figure 2:
The correct setting of the primary CT direction
CTStarPoint is set to FromObject or ToObject .
Positive quantities flow towards the object.
Direction is defined as
The ratios of the main CTs and VTs must be known to use primary system quantities for settings
and calculation in the IED, The user has to set the rated secondary and primary currents and
voltages of the CTs and VTs to provide the IED with this information.
The CT and VT ratio and the name on respective channel is done under Main menu/Hardware/
Analog modules in the Parameter Settings tool.
3.3

Settings

Dependent on ordered IED type.
Table 1:
AISVBAS Non group settings (basic)
Name
Values (Range)
PhaseAngleRef
TRM - Channel 1
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
46
Forward
Protected Object
Line, transformer, etc
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Internal convention of the directionality in the IED
Forward and looks towards the object.
Unit
Step
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Definition of direction
for directional functions
Forward
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Correct Setting is
en05000456_ansi.vsd
Default
Description
TRM - Channel 1
Reference channel for phase angle
presentation
1MRK 506 326-UUS B
Reverse
Set parameter
CT_WyePoint
"FromObject"
SEMOD55040-1 v2
SEMOD129840-4 v2
PID-1938-SETTINGS v5
Line distance protection REL650
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents