ABB Relion 650 Series Technical Manual page 333

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
10.7.2
Functionality
The IEC 61850 generic communication I/O functions (DPGGIO) function block is used to send
double indications to other systems or equipment in the substation. It is especially used in the
interlocking and reservation station-wide logics.
10.7.3
Function block
DPGGIO
OPEN
CLOSE
VALID
IEC09000075_1_en.vsd
IEC09000075 V1 EN-US
Figure 170: DPGGIO function block
10.7.4
Signals
Table 250: DPGGIO Input signals
Name
OPEN
CLOSE
VALID
Table 251: DPGGIO Output signals
Name
POSITION
10.7.5
Settings
The function does not have any parameters available in Local HMI or Protection and Control IED
Manager (PCM600).
10.7.6
Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions (DPGGIO)
function block will send the signals over IEC 61850-8-1 to the equipment or system that requests
these signals. To be able to get the signals, PCM600 must be used to define which function block
in which equipment or system should receive this information.
Line distance protection REL650
Technical manual
POSITION
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
INTEGER
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Open indication
Close indication
Valid indication
Description
Double point indication
Section 10
Control
SEMOD55850-5 v3
SEMOD54710-4 v4
PID-1881-INPUTSIGNALS v6
PID-1881-OUTPUTSIGNALS v6
ABBD8E226199 v2
SEMOD55861-5 v5
327