1MRK 506 326-UUS B
13.6.6.1
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip values are
available on the local HMI. To acquire a complete disturbance report the user must use a PC and -
either the PCM600 Disturbance handling tool - or a FTP or MMS (over 61850) client. The PC can be
connected to the IED front, rear or remotely via the station bus (Ethernet ports).
13.6.6.2
Indications
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged), see Indication section for detailed information.
13.6.6.3
Event recorder
The event recorder may contain a list of up to 150 time-tagged events, which have occurred during
the disturbance. The information is available via the local HMI or PCM600, see Event recorder
section for detailed information.
13.6.6.4
Sequential of events
The sequetial of events may contain a list of totally 1000 time-tagged events. The list information
is continuously updated when selected binary signals change state. The oldest data is overwritten.
The logged signals may be presented via local HMI or PCM600, see Sequential of events section for
detailed information.
13.6.6.5
Trip value recorder
The recorded trip values include phasors of selected analog signals before the fault and during the
fault, see Trip value recorder section for detailed information.
13.6.6.6
Disturbance recorder
Disturbance recorder records analog and binary signal data before, during and after the fault, see
Disturbance recorder section for detailed information.
13.6.6.7
Fault locator
The fault location function calculates the distance to fault, see Fault locator section for detailed
information.
Line distance protection REL650
Technical manual
The maximum number of recordings depend on each recordings total recording
time. Long recording time will reduce the number of recordings to less than 100.
The IED flash disk should NOT be used to store any user files. This might cause
disturbance recordings to be deleted due to lack of disk space.
© Copyright 2011 ABB Power Grids. All rights reserved
Section 13
Monitoring
M12155-175 v3
M12155-87 v4
M12155-89 v4
M12155-177 v5
M12155-91 v4
M12155-97 v4
M12155-186 v3
457