Section 5
Impedance protection
5.8.2
Functionality
Automatic switch onto fault logic, voltage and current based (ZCVPSOF) is a function that gives an
instantaneous trip at closing of breaker onto a fault. A dead line detection check is provided to
activate the function when the line is dead.
Mho distance protections can not operate for switch onto fault condition when the phase voltages
are close to zero. An additional logic based on VI Level is used for this purpose.
5.8.3
Function block
I3P*
V3P*
BLOCK
BC
ZACC
ANSI09000057 V1 EN-US
Figure 82: ZCVPSOF Function block
5.8.4
Signals
Table 54: ZCVPSOF Input signals
Name
I3P
V3P
BLOCK
BC
ZACC
Table 55: ZCVPSOF Output signals
Name
TRIP
146
ZCVPSOF
TRIP
ANSI09000057-1-en.vsd
Type
Default
GROUP
-
SIGNAL
GROUP
-
SIGNAL
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Three phase group signal for current inputs
Three phase group signal for voltage inputs
Block of function
External enabling of SOTF
Distance zone to be accelerated by SOTF
Description
Trip by pilot communication scheme logic
1MRK 506 326-UUS B
SEMOD153644-5 v3
SEMOD156265-4 v4
PID-1521-INPUTSIGNALS v5
PID-1521-OUTPUTSIGNALS v5
Line distance protection REL650
Technical manual