1MRK 506 326-UUS B
Terminal
X339-15
X339-16
X339-17
X339-18
17.3
Outputs
17.3.1
Outputs for tripping, controlling and signalling
Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for controlling
circuit breakers.
Each signal connector terminal is connected with one 14 or 16 Gauge wire. Use 12 or 14 Gauge wire
for CB trip circuit.
Table 541: Output contacts X307, 6U half 19"
Terminal
X307-1
X307-2
X307-3
X307-4
X307-5
X307-6
X307-7
X307-8
X307-9
X307-10
X307-11
X307-12
Line distance protection REL650
Technical manual
Description
-
Common - for inputs 8-9
Binary input 8 +
Binary input 9 +
The connected DC voltage to outputs with trip circuit supervision (TCM) must have
correct polarity or the trip circuit supervision TCSSCBR function will not operate
properly.
Description
Power output 1, normally open (TCM)
-
+
Power output 2, normally open (TCM)
-
+
Power output 3, normally open (TCM)
-
+
Power output 4, normally open
Power output 5, normally open
Power output 6, normally open
© Copyright 2011 ABB Power Grids. All rights reserved
PCM600 info
Hardware module
Hardware channel
instance
BIO_6
BI8
BIO_6
BI9
GUID-F4C2CA65-C912-4023-B6A4-1BEEDFB9FEA9 v2
PCM600 info
Hardware module
Hardware channel
instance
PSM_102
BO1_PO_TCM
PSM_102
BO2_PO_TCM
PSM_102
BO3_PO_TCM
PSM_102
BO4_PO
PSM_102
BO5_PO
PSM_102
BO6_PO
Section 17
IED physical connections
581