ABB Relion 650 Series Technical Manual page 343

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
10.13.3
Signals
Table 267: I103GENCMD Input signals
Name
BLOCK
Table 268: I103GENCMD Output signals
Name
CMD_OFF
CMD_ON
10.13.4
Settings
Table 269: I103GENCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 127
PulseLength
0.000 - 60.000
InfNo
32 - 239
10.14
IED commands with position and select for IEC
60870-5-103 I103POSCMD
10.14.1
Functionality
I103POSCMD has double-point position indicators that are getting the position value as an integer
(for example from the POSITION output of the SCSWI function block) and sending it over IEC
60870-5-103 (1=OPEN; 2=CLOSE); as per standard,
supported.
The BLOCK input will block only the signals in monitoring direction (the position information), not
the commands via IEC 60870-5-103. The SELECT input is used to indicate that the monitored
apparatus has been selected (in a select-before-operate type of control)
Line distance protection REL650
Technical manual
Type
Default
Description
BOOLEAN
0
Block of command
Type
Description
BOOLEAN
Command output OFF
BOOLEAN
Command output ON
Unit
Step
-
1
s
0.001
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
1
Function type (1-255)
0.400
Pulse length
32
Information number for command output
(1-255)
0 and 3 values of the position are not
Section 10
Control
PID-2662-INPUTSIGNALS v4
PID-2662-OUTPUTSIGNALS v4
PID-2662-SETTINGS v4
GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v3
337