ABB Relion 650 Series Technical Manual page 417

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 365: CMMXU Non group settings (advanced)
Name
Values (Range)
ILZeroDb
0 - 100000
ILHiHiLim
0 - 500000
ILHiLim
0 - 500000
ILLowLim
0 - 500000
ILLowLowLim
0 - 500000
ILMin
0 - 500000
ILLimHys
0.000 - 100.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
13.4.3.5
Monitored data
Table 366: CMMXU Monitored data
Name
I_A
IA_ANGL
I_B
IB_ANGL
I_C
IC_ANGL
13.4.4
Phase-phase voltage measurement VMMXU
13.4.4.1
Identification
Function description
Phase-phase voltage measurement
Line distance protection REL650
Technical manual
Unit
Step
m%
1
A
1
A
1
A
1
A
1
A
1
%
0.001
%
0.001
%
0.001
%
0.001
Deg
0.001
Deg
0.001
Deg
0.001
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
IEC 61850
identification
VMMXU
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
500
Zero point clamping
1200
High High limit (physical value)
1100
High limit (physical value)
0
Low limit (physical value)
0
Low Low limit (physical value)
0
Minimum value
5.000
Hysteresis value in % of range and is
common for all limits
0.000
Magnitude factor to calibrate current at
5% of In
0.000
Magnitude factor to calibrate current at
30% of In
0.000
Magnitude factor to calibrate current at
100% of In
0.000
Angle calibration for current at 5% of In
0.000
Angle calibration for current at 30% of In
0.000
Angle calibration for current at 100% of In
Unit
Description
A
IA Amplitude
deg
IA Angle
A
IB Amplitude
deg
IB Angle
A
IC Amplitude
deg
IC Angle
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
U
SYMBOL-UU V1 EN-US
Section 13
Monitoring
PID-1102-MONITOREDDATA v7
GUID-726E0058-033D-4E90-870A-A870ADAD33B0 v1
411

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents