The IB16FCVB function is designed for receiving the integer input from a station computer - for
example, over IEC 61850. If the BLOCK input is activated, it will freeze the logical outputs at the
last value.
Table 349: Outputs and their values when activated
Name of OUTx
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted to boolean by the IB16FCVB
function block.
The operator position input (PSTO) determines the operator place. The integer number that is
communicated to the IB16FCVB can only be written to the block while the PSTO is in position
"Remote". If PSTO is in position "Off" or "Local", then no changes are applied to the outputs.
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Output 1
BOOLEAN
Output 2
BOOLEAN
Output 3
BOOLEAN
Output 4
BOOLEAN
Output 5
BOOLEAN
Output 6
BOOLEAN
Output 7
BOOLEAN
Output 8
BOOLEAN
Output 9
BOOLEAN
Output 10
BOOLEAN
Output 11
BOOLEAN
Output 12
BOOLEAN
Output 13
BOOLEAN
Output 14
BOOLEAN
Output 15
BOOLEAN
Output 16
© Copyright 2011 ABB Power Grids. All rights reserved
Value when activated Value when
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
Section 12
Logic
395