1MRK 506 326-UUS B
Section 14
14.1
Pulse counter PCGGIO
14.1.1
Identification
Function description
Pulse counter
14.1.2
Functionality
Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses
coming from an external energy meter, for calculation of energy consumption values. The pulses
are captured by the BIO (binary input/output) module and then read by the PCGGIO function. A
scaled service value is available over the station bus.
14.1.3
Function block
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
IEC09000335 V2 EN-US
Figure 273: PCGGIO function block
14.1.4
Signals
Table 457: PCGGIO Input signals
Name
BLOCK
READ_VAL
BI_PULSE
RS_CNT
Line distance protection REL650
Technical manual
Metering
IEC 61850
identification
PCGGIO
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC09000335-2-en.vsd
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
identification
PCGGIO
S00947 V1 EN-US
Description
Block of function
Initiates an additional pulse counter reading
Connect binary input channel for metering
Resets pulse counter value
GUID-50478353-2EE5-45ED-8A89-4EB0A0F71314 v2
ANSI/IEEE C37.2
device number
-
PID-1821-INPUTSIGNALS v9
Section 14
Metering
M13394-3 v6
M13400-3 v4
511