1MRK 506 326-UUS B
13.16.5
Settings
Table 434: SSIML (71) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
LevelAlmLimit
0.00 - 25.00
LevelLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tLevelAlarm
0.000 - 60.000
tLevelLockOut
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetLevelAlm
0.000 - 60.000
tResetLevelLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
13.16.6
Operation principle
Insulation liquid monitoring function SSIML (71) is used to monitor oil level in the circuit breaker.
Two binary output signals are used from the circuit breaker to initiate alarm signals, level below
alarm level and level below lockout level. If the input signal LVL_ALM is high, which indicate that
the oil level in the circuit breaker is below alarm level, the output signal LVL_ALM, level below alarm
level, will be initiated after a set time delay and indicate that maintenance of the circuit breaker is
required. Similarly, if the input signal LVL_LO is high, which indicate oil level in the circuit breaker is
below lockout level, the output signal LVL_LO, will be initiated after a time delay. The two time
delay settings,
short sudden changes in the oil level. If the oil level in the circuit breaker goes below the levels for
more than the set time delays the corresponding signals, LVL_ALM, level below alarm level and
LVL_LO, level below lockout level alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms and the input signal BLOCK to block
both alarms and the function.
Line distance protection REL650
Technical manual
Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
tLevelAlarm and tLevelLockOut , are included in order not to initiate any alarm for
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
5.00
Alarm setting for level
3.00
Level lockout setting
30.00
Temperature alarm level setting of the
medium
30.00
Temperature lockout level of the medium
0.000
Time delay for level alarm
0.000
Time delay for level lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for level alarm
0.000
Reset time delay for level lockout
0.000
Reset time delay for temperture lockout
0.000
Reset time delay for temperture alarm
Section 13
Monitoring
PID-1839-SETTINGS v5
GUID-F4340B59-90D0-4EA7-9FD8-F21D425C884A v2