Section 5
Impedance protection
5.6
Phase preference logic PPLPHIZ
5.6.1
Identification
Function description
Phase preference logic
5.6.2
Functionality
Phase preference logic function PPLPHIZ is intended to be used in isolated or high impedance
grounded networks where there is a requirement to trip only one of the faulty lines at cross-
country fault.
Phase preference logic inhibits tripping for single phase-to-ground faults in isolated and high
impedance grounded networks, where such faults are not to be cleared by distance protection.
For cross-country faults, the logic selects either the leading or the lagging phase-ground loop for
measurement and initiates tripping of the preferred fault based on the selected phase preference.
A number of different phase preference combinations are available for selection.
5.6.3
Function block
I3P*
V3P
BLOCK
RELAG
RELBG
RELCG
PHSEL
ANSI09000060 V1 EN-US
Figure 76: PPLPHIZ function block
5.6.4
Signals
Table 42: PPLPHIZ Input signals
Name
I3P
V3P
BLOCK
RELAG
RELBG
RELCG
PHSEL
134
PPLPHIZ
PICKUP
ZREL
ANSI09000060-1-en.vsd
Type
Default
GROUP
-
SIGNAL
GROUP
-
SIGNAL
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
INTEGER
0
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
PPLPHIZ
-
Description
Three phase group signal for current inputs
Three phase group signal for voltage inputs
Block of function
Release condition for the A to ground loop
Release condition for the B to ground loop
Release condition for the C to ground loop
Integer coded external release signal
1MRK 506 326-UUS B
ANSI/IEEE C37.2
device number
-
PID-1444-INPUTSIGNALS v5
Line distance protection REL650
Technical manual
SEMOD151937-2 v2
SEMOD151924-4 v3
SEMOD172690-4 v4