1MRK 506 326-UUS B
6.15.3.1
Identification
Function description
Directional underpower protection
6.15.3.2
Function block
I3P*
V3P*
BLOCK
BLK1
BLK2
ANSI08000507 V1 EN-US
Figure 118: GUPPDUP (37) function block
6.15.3.3
Signals
Table 150: GUPPDUP (37) Input signals
Name
I3P
V3P
BLOCK
BLK1
BLK2
Table 151: GUPPDUP (37) Output signals
Name
TRIP
TRIP1
TRIP2
BFI_3P
PICKUP1
Table continues on next page
Line distance protection REL650
Technical manual
GUPPDUP (37)
TRIP
TRIP1
TRIP2
BFI_3P
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI08000507-1-en.vsd
Type
GROUP
SIGNAL
GROUP
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
GUPPDUP
P <
SYMBOL-LL V1 EN-US
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from stage 1
Trip signal from stage 2
General pickup signal
Pickup signal from stage 1
Current protection
ANSI/IEEE C37.2
device number
37
PID-2724-INPUTSIGNALS v5
PID-2724-OUTPUTSIGNALS v5
Section 6
SEMOD158941-2 v4
SEMOD172623-4 v4
223