1MRK 506 326-UUS B
Section 11
11.1
Scheme communication logic for distance or overcurrent
protection ZCPSCH (85)
11.1.1
Identification
Function description
Scheme communication logic for
distance or overcurrent protection
11.1.2
Functionality
To achieve instantaneous fault clearance for all line faults, a scheme communication logic is
provided. All types of communication schemes for example, permissive underreaching, permissive
overreaching, blocking, unblocking, intertrip are available.
11.1.3
Function block
BLOCK
BLKTR
BLKCS
CS_STOP
PLTR_CRD
CSOR
CSUR
CR
CR_GUARD
ANSI09000004 V1 EN-US
Figure 178: ZCPSCH (85) function block
11.1.4
Signals
Table 272: ZCPSCH (85) Input signals
Name
BLOCK
BLKTR
BLKCS
CS_STOP
PLTR_CRD
Table continues on next page
Line distance protection REL650
Technical manual
Scheme communication
ZCPSCH (85)
TRIP
CS
CRL
LCG
ANSI09000004-1-en.vsd
Type
Default
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
ZCPSCH
Description
0
Block of function
0
Block pilot (communication assisted) trip
0
Block pilot channel start
0
Block of channel start (CS) due to reverse fault detection
0
Signal to be used for coordinating local pilot tripping with the
channel receive (CR) signal
Scheme communication
GUID-3A679DF1-61BE-4AA3-BF11-E20CAB531725 v1
ANSI/IEEE C37.2
device number
-
85
Section 11
M14854-1 v3
M13860-3 v5
M13866-3 v5
PID-1883-INPUTSIGNALS v5