ABB Relion 650 Series Technical Manual page 141

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 43: PPLPHIZ Output signals
Name
PICKUP
ZREL
5.6.5
Settings
Table 44: PPLPHIZ Group settings (basic)
Name
Values (Range)
OperMode
No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
PU27PN
10.0 - 100.0
PU27PP
10.0 - 100.0
3V0PU
5.0 - 300.0
Pickup_N
10 - 200
tVN
0.000 - 60.000
tOffVN
0.000 - 60.000
tIN
0.000 - 60.000
Table 45: PPLPHIZ Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
5.6.6
Operation principle
5.6.6.1
Operation principle
Phase preference logic PPLPHIZ has 10 operation modes, which can be set by the parameter
OperMode . The different modes and their explanation are shown in table
between cyclic and acyclic operation can be explained by the following example. Assume a A fault
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Indicates start for ground fault(s), regardless of direction
INTEGER
Integer coded output release signal
Unit
Step
-
-
%VB
1.0
%VB
1.0
%VB
1.0
%IB
1
s
0.001
s
0.001
s
0.001
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
No Filter
Operating mode (c=cyclic,a=acyclic)
70.0
Operate value of phase undervoltage in %
of VBase
50.0
Operate value of line to line undervoltage
in % of VBase
20.0
Operate value of residual voltage in % of
VBase
20
Operate value of residual current in % of
IBase
0.100
Pickup delay for residual voltage
0.100
Dropoff delay for residual voltage
0.150
Pickup delay for residual current
Default
Description
1
Selection of one of the Global Base Value
groups
Section 5
Impedance protection
PID-1444-OUTPUTSIGNALS v5
PID-1444-SETTINGS v6
SEMOD151916-4 v4
46
below. The difference