Section 15
Station communication
15.6.3
Function block
BLOCK
IEC10000250 V1 EN-US
Figure 279: GOOSEINTRCV function block
15.6.4
Signals
Table 480: GOOSEINTRCV Input signals
Name
BLOCK
Table 481: GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST
15.6.5
Settings
Table 482: GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.6.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
528
GOOSEINTRCV
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd
Type
BOOLEAN
Type
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
The input of this GOOSE block must be crossed in the SMT to receive the integer
values.
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
0
Block of function
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Step
Default
-
Disabled
1MRK 506 326-UUS B
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
Description
Operation Off/On
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v1
Line distance protection REL650
Technical manual
PID-2529-INPUTSIGNALS v6
PID-2529-OUTPUTSIGNALS v6
PID-2529-SETTINGS v6