ABB Relion 650 Series Technical Manual page 125

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
5.4.4
Signals
Table 31:
Name
I3P
V3P
BLOCK
Zpick up
TR3PH
Table 32:
Name
PICKUP
PU_A
PU_B
PU_C
PHG_FLT
PHSCND
DLECND
PU_BLF
5.4.5
Settings
Table 33:
FMPSPDIS Group settings (basic)
Name
Values (Range)
IMaxLoad
10 - 5000
RLd
1.00 - 3000.00
LdAngle
5 - 70
BlinderAng
5 - 90
Line distance protection REL650
Technical manual
FMPSPDIS Input signals
Type
Default
GROUP
SIGNAL
GROUP
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
FMPSPDIS Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
INTEGER
INTEGER
Unit
%IB
ohm/p
Deg
Deg
© Copyright 2011 ABB Power Grids. All rights reserved
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Pick up from under impedance function
0
Three phase tripping initiated
Description
General pickup signal
Fault detected in phase A
Fault detected in phase B
Fault detected in phase C
Ground fault detected
Binary coded starts from phase selection
Binary coded starts from load encroachment only
Binary coded starts from fund. frequency based blinders
Step
Default
1
200
0.01
80.00
1
20
1
80
Impedance protection
Description
Maximum load for identification of three
phase fault in % of IBase
Load resistive reach in ohm/phase
Load encroachment inclination of load
angular sector
Blinder angle
Section 5
PID-1571-INPUTSIGNALS v6
PID-1571-OUTPUTSIGNALS v6
PID-1571-SETTINGS v6
119