1MRK 506 326-UUS B
Standard signals are always presented in the IED, see
Hardware dependent internal signals are collected depending on the hardware configuration,
see
Explanations of internal signals are listed in
Table 493: SELFSUPEVLST standard internal signals
Name of signal
Internal Fail
Internal Warning
Real Time Clock Error
Time Synch Error
Runtime App Error
Runtime Exec Error
IEC61850 Error
SW Watchdog Error
Settings Changed
Setting Group Changed
Change Lock
File System Error
DNP3 Error
Table 494: Self-supervision's hardware dependent internal signals
Card
PSM
TRM
COM
BIO
AIM
RTD
Table 495: Explanations of internal signals
Name of signal
Internal Fail
Internal Warning
Real Time Clock Error
Table continues on next page
Line distance protection REL650
Technical manual
Table
494.
Name of signal
PSM-Error
TRM-Error
COM-Error
BIO-Error
AIM-Error
RTD-Error
© Copyright 2011 ABB Power Grids. All rights reserved
Table
495.
Description
Internal fail status
Internal warning status
Real time clock status
Time synchronization status
Runtime application error status
Runtime execution error status
IEC 61850 error status
SW watchdog error status
Settings changed
Setting groups changed
Change lock status
Fault tolerant file system status
DNP3 error status
Description
Power supply module error status
Transformator module error status
Communication module error status
Binary input/output module error status
Analog input module error status
Resistance temperature detector / mA-output module error
status
Reasons for activation
This signal will be active if one or more of the following internal signals are
active; Real Time Clock Error, Runtime App Error, Runtime Exec Error, SW
Watchdog Error, File System Error
This signal will be active if one or more of the following internal signals are
active; IEC 61850 Error, DNP3 Error
This signal will be active if there is a hardware error with the real time
clock.
Table
493.
Section 16
Basic IED functions
541