ABB Relion 650 Series Technical Manual page 227

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
6.15.2.3
Signals
Table 144: GOPPDOP (32) Input signals
Name
I3P
V3P
BLOCK
BLK1
BLK2
Table 145: GOPPDOP (32) Output signals
Name
TRIP
TRIP1
TRIP2
BFI_3P
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
6.15.2.4
Settings
Table 146: GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
OverPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.010 - 6000.000
OpMode2
Disabled
OverPower
Table continues on next page
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip signal from stage 1
BOOLEAN
Trip signal from stage 2
BOOLEAN
General pickup signal
BOOLEAN
Pickup signal from stage 1
BOOLEAN
Pickup signal from stage 2
REAL
Active Power
REAL
Active power in % of calculated power base value
REAL
Reactive power
REAL
Reactive power in % of calculated power base value
Unit
Step
-
-
-
-
%
0.1
Deg
0.1
s
0.001
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
OverPower
Operation mode 1
1.0
Power setting for stage 1 in % of
calculated power base value
0.0
Characteristic angle for stage 1
1.000
Trip delay for stage 1
OverPower
Operation mode 2
Section 6
Current protection
PID-2725-INPUTSIGNALS v5
PID-2725-OUTPUTSIGNALS v5
PID-2725-SETTINGS v5