ABB Relion 650 Series Technical Manual page 507

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
13.18.3
Signals
Table 441: I103MEAS Input signals
Name
BLOCK
I_A
I_B
I_C
IN
V_A
V_B
V_C
V_AB
V_N
P
Q
F
13.18.4
Settings
Table 442: I103MEAS Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
MaxIa
1 - 99999
MaxIb
1 - 99999
MaxIc
1 - 99999
MaxIN
1 - 99999
MaxVa
0.05 - 2000.00
MaxVb
0.05 - 2000.00
MaxVc
0.05 - 2000.00
MaxVa-Vb
0.05 - 2000.00
MaxVn
0.05 - 2000.00
MaxP
0.00 - 2000.00
MaxQ
0.00 - 2000.00
MaxF
50.0 - 60.0
Line distance protection REL650
Technical manual
Type
Default
Description
BOOLEAN
0
Block of service value reporting
REAL
0.0
Service value for current phase A
REAL
0.0
Service value for current phase B
REAL
0.0
Service value for current phase C
REAL
0.0
Service value for residual current IN
REAL
0.0
Service value for voltage phase A
REAL
0.0
Service value for voltage phase B
REAL
0.0
Service value for voltage phase C
REAL
0.0
Service value for voltage phase-phase A-B
REAL
0.0
Service value for residual voltage VN
REAL
0.0
Service value for active power
REAL
0.0
Service value for reactive power
REAL
0.0
Service value for system frequency
Unit
Step
-
1
A
1
A
1
A
1
A
1
kV
0.05
kV
0.05
kV
0.05
kV
0.05
kV
0.05
MW
0.05
MVA
0.05
Hz
10.0
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
1
Function type (1-255)
3000
Maximum current phase A
3000
Maximum current phase B
3000
Maximum current phase C
3000
Maximum residual current IN
230.00
Maximum voltage for phase A
230.00
Maximum voltage for phase B
230.00
Maximum voltage for phase C
400.00
Maximum voltage for phase-phase A-B
230.00
Maximum residual voltage VN
1200.00
Maximum value for active power
1200.00
Maximum value for reactive power
50.0
Maximum system frequency
Section 13
Monitoring
PID-2652-INPUTSIGNALS v4
PID-2652-SETTINGS v4
501